Permit Number: T04CM05376
Parcel: 141148150

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM05376
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Appliances to be directly connected to the water supply system (e.g. coffee brewer, ice/soda dispenser) that do not have listed, integral backflow preventers or integral air gaps may require reduced pressure principle backflow preventers. Please submit equipment sheets for determination. Reference Section 603.0, UPC 1994.
2. Indicate the type of backflow preventer that is to be used to protect the water supply to the carbonator. Reference Section 603.3.12, UPC 1994 with AZ State amendments.
3. Provide water pressure and water pipe sizing calculations. Reference Section 610.5, UPC 1994.
4. Calculate the water demand for the water supply outlets not listed in Table 6-3 using the public fixture units shown at the bottom of Table 6-3. Reference Section 610.3, UPC 1994.
5. Limit the water velocity to less than 8 fps for the copper piping (e.g. HWR). Reference Section A 6.1, UPC 1994 and IAPMO IS 3-93, Section 610.0.
01/28/2005 ROBERT SHERRY WATER REVIEW Approved
01/28/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations to show that the common ventilation system is sized in accordance with Section 403.3.2, IMC 2000.
2. Show how the sequence of operation for the restroom exhaust fan prevents the restroom from being positively pressurized.
02/04/2005 TACHONG1 BUILDING-COMMERCIAL REVIEW Needs Review
02/04/2005 TACHONG1 WWM REVIEW Needs Review
02/04/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
12/14/2004 JIM EGAN FIRE REVIEW Denied Need complete plans for structural revisions.
12/14/2004 DAN CASTRO ZONING REVIEW Approved
12/14/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/04/2005 TAMI ACHONG OUT TO CUSTOMER Completed