Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM05376
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/28/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Appliances to be directly connected to the water supply system (e.g. coffee brewer, ice/soda dispenser) that do not have listed, integral backflow preventers or integral air gaps may require reduced pressure principle backflow preventers. Please submit equipment sheets for determination. Reference Section 603.0, UPC 1994. 2. Indicate the type of backflow preventer that is to be used to protect the water supply to the carbonator. Reference Section 603.3.12, UPC 1994 with AZ State amendments. 3. Provide water pressure and water pipe sizing calculations. Reference Section 610.5, UPC 1994. 4. Calculate the water demand for the water supply outlets not listed in Table 6-3 using the public fixture units shown at the bottom of Table 6-3. Reference Section 610.3, UPC 1994. 5. Limit the water velocity to less than 8 fps for the copper piping (e.g. HWR). Reference Section A 6.1, UPC 1994 and IAPMO IS 3-93, Section 610.0. |
01/28/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
01/28/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations to show that the common ventilation system is sized in accordance with Section 403.3.2, IMC 2000. 2. Show how the sequence of operation for the restroom exhaust fan prevents the restroom from being positively pressurized. |
02/04/2005 | TACHONG1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
02/04/2005 | TACHONG1 | WWM | REVIEW | Needs Review | |
02/04/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
12/14/2004 | JIM EGAN | FIRE | REVIEW | Denied | Need complete plans for structural revisions. |
12/14/2004 | DAN CASTRO | ZONING | REVIEW | Approved | |
12/14/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/04/2005 | TAMI ACHONG | OUT TO CUSTOMER | Completed |