Permit Number: T04CM04578
Parcel: 14028001A

Address:
6100 S TUCSON BL

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04578
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2004 JIM EGAN FIRE REVIEW Approved
10/14/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/14/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM04578 DENIED 10/14/04

1. Sheet M-2 describes a 30 HP exhaust fan. Not on electrical plans. Please coordinate with Mechanical and clarify.
2. Discharge pump is shown as 3 HP on line diagram. VFD size is 1 HP and fusing appears to correspond to a 1 HP motor. Pls clarify.
3. Pls clarify the wording on the line diagram for the Backflash Pump which reads "NEW CP - 4 2HP". Are there four motors?
10/14/2004 ROBERT SHERRY WATER REVIEW Approved
10/14/2004 DAN CASTRO ZONING REVIEW Approved
10/14/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations to show that the design of the exhaust systems comply with the requirements of Section 510, IMC 2000. Verify that the operation of the booster blower will not adversely effect the operation of the exhaust from the evaporator. Indicate the materials being exhausted and their concentrations.
2. Provide balancing information for the modifications to the four exhaust systems.
3. Clarify keynotes 23 and 42.
4. How will the additional exhaust volumes effect the make-up air to the area.
10/14/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
10/28/2004 CAGUILA1 WWM REVIEW Passed
10/28/2004 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review