Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM04578
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/14/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
10/14/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
10/14/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM04578 DENIED 10/14/04 1. Sheet M-2 describes a 30 HP exhaust fan. Not on electrical plans. Please coordinate with Mechanical and clarify. 2. Discharge pump is shown as 3 HP on line diagram. VFD size is 1 HP and fusing appears to correspond to a 1 HP motor. Pls clarify. 3. Pls clarify the wording on the line diagram for the Backflash Pump which reads "NEW CP - 4 2HP". Are there four motors? |
10/14/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/14/2004 | DAN CASTRO | ZONING | REVIEW | Approved | |
10/14/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations to show that the design of the exhaust systems comply with the requirements of Section 510, IMC 2000. Verify that the operation of the booster blower will not adversely effect the operation of the exhaust from the evaporator. Indicate the materials being exhausted and their concentrations. 2. Provide balancing information for the modifications to the four exhaust systems. 3. Clarify keynotes 23 and 42. 4. How will the additional exhaust volumes effect the make-up air to the area. |
10/14/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
10/28/2004 | CAGUILA1 | WWM | REVIEW | Passed | |
10/28/2004 | CAGUILA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |