Permit Number: T04CM04073
Parcel: 110034830

Review Status: Completed

Review Details: SITE

Permit Number - T04CM04073
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2004 Jim Egan FIRE REVIEW Approved
09/13/2004 ANDREW CONNOR NPPO REVIEW Passed
09/13/2004 Andrew Connor LANDSCAPE REVIEW Passed
09/30/2004 LEE JACOBS LANDFILL REVIEW Denied This project requires a self-certification -based on its proximity to the Walnut Landfill.
10/05/2004 PAUL MACHADO ENGINEERING REVIEW Denied To: Bruce M. Patton, P.E. DATE: October 5, 2004
Rick Engineering Co.
1745 E. River Road
Tucson, Arizona 85718

SUBJECT: 3950 E. Paradise Falls Dr., Davidson Elementary School
Site plan T04CM04073 (First Review)
Grading plan T04BU02233 (First Review)
T13S, R14E, Section 27

RESUBMITTAL REQUIRED: Site Plan, Grading Plan, Floodplain Use Permit and Hydrology Report.

The Site Plan (SP), Grading Plan (GP), Floodplain Use Permit (FUP) and Hydrology Report (HP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:
1. This parcel is located in the FEMA flood zone "shaded x", "un-shaded x" and the "AE" zone on panel 1643. It is also important to note that school sites may be exempt from the LUC, they are not exempt from the FEMA floodplain requirements. Please submit a Site Plan, Grading Plan, Floodplain Use Permit and Hydrology Report with all the pertinent information contained on each plan.
Grading Plan:
1. Please see Site Plan comment.
2. Please include a response letter to the comments along with the corrected copies of the GP.
3. (3) copies of the grading plan and SWPPP are required at submittal.
Hydrology Report:
1. Please include a response letter to the comments along with the corrected copies of the HR.
2. A Hec-Ras will be required for an encroachment analysis of the Rillito Creek.
3. A HR is required for parcels affected by 100 year flows of 100 cfs, of more per S.M.D.D.F.M., chap. II, 2.1.2.
4. The content and format of the Hydrology report should follow S.M.D.D.F.M., chap. II, 2.1.3.
5. Please show the project address on the cover of the Hydrology report.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210, (520) 791-5550 x1193 office, (520) 879-8010 fax, C:/3950 E. Paradise Falls Dr. site1
10/08/2004 DAN CASTRO HANDICAP-SITE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/11/2004 LISA LESNY OUT TO CUSTOMER Completed
10/11/2004 ANGIE SHOFFSTALL REJECT SHELF Completed