Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2004 Jim Egan FIRE REVIEW Approved
09/02/2004 Joseph Linville NPPO REVIEW Approved Exception
09/07/2004 JOE LINVILLE LANDSCAPE REVIEW Approved
09/17/2004 Doug Williams ENGINEERING REVIEW Denied SUBJECT: Site Review - New Senior Center
REVIEWER: Doug Williams
DATE: 20 September 2004
ACTIVITY NUMBERS: T04CM03923/T04BU02164

SUMMARY: Engineering Division has reviewed the Site Plan received on 1 September 2004. No grading plan could be found with the submittal package. Approval of the site plan is not recommended at this time. Please address the following comments in a response letter, and on a revised site plan:

SITE PLAN
1. Sheet C1.1.1 identifies Missiondale Rd. as being vacated yet provides right of way dimensioning. Please revise the plan to reflect current conditions. Provide recording information on the plan for the right of way vacation, if this has occurred.
2. Depict drainage patterns and finished grades (Development Standard - DS - 2-02.2.1.16).
3. Provide estimated cut/fill quantities (DS 2-02.2.1 A17).
4. Provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent, and Benchmark based on City of Tucson Datum, including City Field Book and Page number. Optionally, GPS Control point data may be referenced as a basis of elevation, if - include the basis of elevation on the site plan (DS 2-02.2.1.23).
5. Depict and label roof drainage direction(s)and sidewalk scuppers at all downspout locations for conveyance of 10-year flows, minimum, under all sidewalk areas (DS 2-08.4.1 E & 3-01.4.4 F).
6. Please provide the total area to be disturbed. Should the area be one acre or greater, or if this proposed development is part of a larger common plan, Stormwater Pollution Prevention Plan requirements must be met. See the enclosed flyer, and visit http://www.azdeq.gov/function/forms/appswater.html and http://www.azdeq.gov/environ/water/permits/download/cswppp.pdf for Arizona Pollutant and Discharge Elimination System (AZPDES) guidelines and information, a construction Stormwater Pollution Prevention Plan (SWPPP) checklist, plan preparation and submittal requirements.
* Please note that additional comments may be necessary upon resubmittal, depending upon percent expansion calculation approval by Zoning Review Section, and the nature and extent of revisions that occur to the plans.
* A right of way permit will be required for any work in the public right of way. Contact Permits and Codes - Tucson Department of Transportation (TDOT) at 791-5100 for questions.
If you have any questions, I can be reached at 791-5550, extension 1189 or Dwillia1@ci.tucson.az.us.

Doug Williams
Sr. Engineering Associate
Engineering Division
Development Services Department
09/20/2004 Daniel Castro ZONING REVIEW Denied COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were
addressed. (CODE SECTION/ DEVELOPMENT STANDARD)

1. The following comments are based on 21.93% cumulative building area expansion resulting in a full code compliance review of the expansion area only.

2. Add lot dimensions and bearings to the overall site plan. (D.S. 2-02.2.1.A.5)

3. Under the parking calculations block on sheet TS2.0, revise the total number of vehicle parking spaces required for the pool to 49. (6100/125 = 48.8). This revision changes the total number of vehicle parking spaces required for the overall site to 840. Revise grand total listed under the parking calculations block as required, and revise the note which states the number of spaces required for waiver to 40 spaces. (LUC 3.3.4) (D.S. 2-02.2.1.A.8)

4. Provide disabled pedestrian access path to building entrance from all new disabled access aisles. Access aisles serving passenger loading zones shall comply with Section 302 and Sections 503.3.1 through 503.3.3. Access aisles shall be part of the accessible route to the building or facility entrance and shall comply with Section 402. (ICC/ANSI A117.1-1998)

5. Indicate the bicycle parking space location/s graphically and by keynote on sheet C1.1.1. In addition provide a fully dimensioned detail for both Class 1 and Class 2 spaces. (D.S. 2-02.2.1.A.9) (D.S. 2-09)

6. Dimension all PAAL widths. (D.S. 2-02.2.1.A.11)

7. If applicable, all existing or proposed easements must be shown on the plan including width, type, and recording docket and page reference. (D.S. 2-02.2.1.A.20)

8. One (1) Class 1 bicycle parking space is required. Waiver to be applied for.

9. Provide a copy of the approved Administrative waiver with the resubmittal of this site plan.

10. Review of this plan by the Zoning Review Section may be done over the counter. Please call me to set an appointment.


If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608.
09/21/2004 DAN CASTRO HANDICAP-SITE REVIEW Denied refer to zoning review comments.