Permit Number: T04CM03805
Parcel: 138241610

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03805
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
08/23/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide riser diagrams for water and waste systems.
2. Provide COT Activity Number and reference drawings showing the removal of the existing restrooms.
08/23/2004 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied
08/23/2004 MELISSA POULIN WWM REVIEW Approved
08/23/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
08/23/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/23/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM03805 DENIED 8/23/04
1.It appears that Ckts 26, 28, 30, AND 32 should be counted at 720 VA each. Looks like some receptacle circuit designations got added after computer-drafting. Please correct/clarify.
2. Please count show windows as continuous loads. Reference Annex D Example D3.
08/23/2004 ROBERT SHERRY WATER REVIEW Approved
08/23/2004 JIM EGAN FIRE REVIEW Approved