| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/18/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 08/23/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide riser diagrams for water and waste systems. 2. Provide COT Activity Number and reference drawings showing the removal of the existing restrooms. |
| 08/23/2004 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 08/23/2004 | MELISSA POULIN | WWM | REVIEW | Approved | |
| 08/23/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/23/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/23/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM03805 DENIED 8/23/04 1.It appears that Ckts 26, 28, 30, AND 32 should be counted at 720 VA each. Looks like some receptacle circuit designations got added after computer-drafting. Please correct/clarify. 2. Please count show windows as continuous loads. Reference Annex D Example D3. |
| 08/23/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/23/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved |