Permit Number: T04CM03716
Parcel: 138240850

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM03716
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. "Since the repair area has been designated as Class I Division 2, the plans would need to be sealed by a Registered Electrical Engineer. The Electrical Plans Examiner, on subsequent submittal, would verify compliance with all requisite NEC and NFPA requirements. " This comment was made on the first submittal. Response indicates that area is Classified as Class I Division 2. Engineering Registrant shall clearly and graphically define the extent of such classified area on the plans. An attempt to do so was made on the plans sealed 8/12/04, but such designation has been removed from plans on subsequent submittals. After Registrant has identified the classified area on the plans, Electrical Plans Examiner shall evaluate compliance with such requirements as NEC 511.3 (B) (1), 511.7, 511.9, 511.12, NEC Article 501, and NFPA 88B (Standard for Repair Garages).

2. Please coordinate and correct for Mechanical Comments #3 and #5 per Bob Sherry, Mechanical Plans Examiner.
01/11/2005 DAVID RIVERA ZONING REVIEW Approved
12/21/2004 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide calculations to show that the common ventilation system for FC-1 is sized in accordance with Section 403.3.2, IMC 2000.
2. Comment not adequately addressed. The installation information provided does not show that the installation (shown in detail 4/M3.0) conforms to the manufacturer's recommendations. Coordinate the installation with the architectural drawings (e.g. A2.0). Show that the clearance to combustibles complies with the manufacturer's listing information. Reference Section 106.3.1, IMC 2000.
12/21/2004 Christy Foreman BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 12/22/04
ACTIVITY NUMBER: T04CM03716
PROJECT NAME: NEW OFFICE BLDG. / MAINTENANCE
PROJECT ADDRESS: 6720 S. RENAISSANCE DR.
ARCHITECT / ENGINEER: PETER MCBRIDE, ARCHITECT WEST
PROJECT REVIEWER: CHRISTY FOREMAN



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.


1. 1009.4 Stairway landings - dimension landing at top of stair must be at least the width of the stair in the direction of travel.
2. Provide cross section through stairwell detailing structural members and connections.
3. Provide structural calculations for new framing members at stairwell. GLB 5 1/8" x 12".
12/21/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the gas loads for the infrared heaters as shown on sheet P2.0 to coordinate with the equipment specified on sheet M2.0. Reference Section 103.2.3, UPC 1994.
2. Based on the provided water calculations, some of the water piping (see detail 1/P2.0) is undersized. Revise the sizes as required or provide calculations to show that the pipe sizes are adequate for the application. Reference Appendix A, UPC 1994.
3. Revise the electrical information for the water heater shown on sheets P2.0 and E3.0 to coordinate with the specified water heater. Reference Section 103.2.3, UPC 1994.
4. Clarify the difference between the "bleed line" and the drain line for the evaporative coolers as shown on detail 2/M3.0. Specify how they two lines are to be terminated (i.e. where and how). Reference Section 313.6, UPC 1994.
5. Show the location and arrangement of the specified air compressor and its accessory equipment on the drawing. Coordinate the new equipment with the electrical drawings. Reference Section 103.2.3, UPC 1994.
12/21/2004 DOUG WILLIAMS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/11/2005 BETH GRANT OUT TO CUSTOMER Completed