Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM03394
Parcel: 11415008U

Review Status: Completed

Review Details: 3RD PARTY REVIEW-REVISION/OTHER

Permit Number - T04CM03394
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2005 CAGUILA1 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Approved
05/10/2005 WILDAN 3RD PARTY REVIEW-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/13/2005 ANGIE SHOFFSTALL APPROVAL SHELF Completed
05/13/2005 CINDY AGUILAR OUT TO CUSTOMER Completed