Permit Number - T04CM02514
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/15/2004 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Please provide a cut sheet of the phase converter. Plans Examiner will pay special attention to how such a converter will derive a neutral on its output. 2. Provide fault calculations for the single phase power. 3. Main Bonding Jumper and Grounding Electrode Conductor should be installed at the 100A 2-P disconnect immediately on the load side of the meter. Reference NEC 250.26 (1), 250.28, 250.24 (A), Article 100. 4. From the Line Diagram it appears that the GND installed at the Phase Converter is existing. Pls clarify. 5. Compressors were in original submittal. They have been removed this submittal, but Keynotes and Notes still address them. Please clarify. 6. Please indicate size, type, and location of 5 HP Pump and pump branch circuit overcurrent protective devices. |