Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address:
5051 E GLENN ST
Address NEW:
5051 E GLENN ST
Apply Date:
06/03/2004
Applicant:
STEVE GREGOR
Description:
ELECTRIC FOR PRIVATE SEWER LIFT STATION
Contractors:
  • EAGLE ROCK CONSTRUCTION ,

Permit Reviews

Permit Number - T04CM02514
Permit Status: Expired
Permit Description: ELECTRIC FOR PRIVATE SEWER LIFT STATION
Start Date Submittal Complete Date Status  
01/11/2005 REVISION - 2ND 01/13/2005 COMPLETED Review Details
04/13/2005 REVISION 04/13/2005 COMPLETED Review Details
04/13/2005 REVISION 04/21/2005 COMPLETED Review Details
06/03/2004 OTHER 06/04/2004 COMPLETED Review Details
06/17/2004 3RD PARTY REVIEW-COMMERCIAL 07/01/2004 COMPLETED Review Details
07/01/2004 POST 3RD PARTY REVIEW 09/07/2004 COMPLETED Review Details
11/08/2004 REVISION - WALK THRU 11/10/2004 COMPLETED Review Details
11/10/2004 REVISION 11/16/2004 COMPLETED Review Details
12/02/2004 RESUBMITTAL 12/02/2004 COMPLETED Review Details
12/02/2004 RESUBMITTAL 01/13/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T04CM02514
Permit Status: Expired
Permit Description: ELECTRIC FOR PRIVATE SEWER LIFT STATION
Total Outstanding Activity Conditions - 1
Date Name
06/03/2004 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T04CM02514
Permite Description: ELECTRIC FOR PRIVATE SEWER LIFT STATION
Total Outstanding Inspections - 4
Last Inspection Date Description Inspector Results Comments
11/15/2004 PLUMBING - ROUGH, SOIL N/A Not ready for Inspection IVRS - Inspection :*
11/15/2004 PLUMBING - SEWER HCS CONNECT N/A Not ready for Inspection IVRS - Inspection :*/PRIVATE SEWAGE COLLECTION SYSTEM COVERED WITHOUT INSP. TALK WITH STEVE LONG 791-5550 EX. 1147
11/15/2004 PLUMBING - TEMP POWER FOR TEST N/A Not ready for Inspection IVRS - Inspection :*
11/15/2004 PLUMBING - FINAL N/A Not ready for Inspection IVRS - Inspection :*

Completed Inspections

Permit Status: Expired
Permit Number: T04CM02514
Permit Description: ELECTRIC FOR PRIVATE SEWER LIFT STATION
Total Completed Inspections - 6
Date Description Inspector Results Comments
10/20/2004 ELECTRIC - FINAL RMAJUTA Approved IVRS - Inspection :
See detailed listing on site.| 999*1)PROVIDE PLANS THAT SHOW HOW JOB HAS BEEN INSTALLED 2)SHOW CORRECT WIRE SIZES, PANEL SIZES 3)PLAN SHOWS CORDS FROM PUMP GOING DIRECTLY TO CONTROL PANEL - NO J-BOX OR SPLICING 4)2 1/2" RISER TO BE BONDED TO ENCLOSURE 5)PANEL SCHEDULE TO BE FILLED OUT 6)SEAT TIGHT TO CARRY AN EQUIPMENT GROUND 7)UNDERGROUND VERFIED 8)SUBMITTALS ON PUMPS & CORDS 9)SEAL PENETRATIONS TO WELL
10/20/2004 OUTDOOR LIGHTING FINAL RMAJUTA Approved IVRS - Inspection :
See detailed listing on site.| 999*
10/20/2004 ELECTRIC - INTERMEDIATE RMAJUTA Approved IVRS - Inspection :*
10/20/2004 ELECTRIC - UNDERGROUND RMAJUTA Approved IVRS - Inspection :
See detailed listing on site.| 999*
10/20/2004 ELECTRIC - UFER RMAJUTA Approved IVRS - Inspection :*
05/10/2005 TEP CLEARANCE - AM JKOZUCH Approved ECO