Permit Number: T04CM02431
Parcel: 10819009B

Address:
4798 N 1ST AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM02431
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2004 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the ventilation calculations for FCU-3 to comply with the requirements of Section 403.3.2, IMC 2000.
2. Provide structural calculations for the kitchen hood. Reference Section 507.6, IMC 2000.
08/06/2004 JIM TATE ENGINEERING REVIEW Approved Flood Use Permit T04OT00840 by M. Flick.
08/06/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. An atmospheric vacuum breaker is not appropriate for use with an ice machine due to the valves downstream of the vacuum breaker. If the ice machine is equipped with pumps for water control, a reduced pressure backflow preventer will be required. Reference Section 603.2, UPC 1994.
2. Revise the water piping to coordinate with the revised water calculations. Coordinate the riser diagram with the plumbing plan.
3. Provide upper terminal cleanout for the pumped drain from the wash rack. Reference Section 710.7, UPC 1994.
4. Comment not addressed. Provide roof drainage calculations along with the sizes of the roof drains, overflows, and rain leaders.
5. Coordinate the keynotes on sheet P1.1 with the current design.
08/10/2004 GERRY KOZIOL WWM REVIEW Denied waste water-cannot drain exterior wash rack to sewer. Needsww/imc review of oil/sand separator. Tom Tomchak-579-5771.
Need to show location/method of connection to public sewer.
08/18/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved
08/18/2004 David Rivera ZONING REVIEW Approved
08/20/2004 TACHONG1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/20/2004 TAMI ACHONG OUT TO CUSTOMER Completed