Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM02431
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/06/2004 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the ventilation calculations for FCU-3 to comply with the requirements of Section 403.3.2, IMC 2000. 2. Provide structural calculations for the kitchen hood. Reference Section 507.6, IMC 2000. |
| 08/06/2004 | JIM TATE | ENGINEERING | REVIEW | Approved | Flood Use Permit T04OT00840 by M. Flick. |
| 08/06/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. An atmospheric vacuum breaker is not appropriate for use with an ice machine due to the valves downstream of the vacuum breaker. If the ice machine is equipped with pumps for water control, a reduced pressure backflow preventer will be required. Reference Section 603.2, UPC 1994. 2. Revise the water piping to coordinate with the revised water calculations. Coordinate the riser diagram with the plumbing plan. 3. Provide upper terminal cleanout for the pumped drain from the wash rack. Reference Section 710.7, UPC 1994. 4. Comment not addressed. Provide roof drainage calculations along with the sizes of the roof drains, overflows, and rain leaders. 5. Coordinate the keynotes on sheet P1.1 with the current design. |
| 08/10/2004 | GERRY KOZIOL | WWM | REVIEW | Denied | waste water-cannot drain exterior wash rack to sewer. Needsww/imc review of oil/sand separator. Tom Tomchak-579-5771. Need to show location/method of connection to public sewer. |
| 08/18/2004 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/18/2004 | David Rivera | ZONING | REVIEW | Approved | |
| 08/20/2004 | TACHONG1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/20/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |