Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM02409
Parcel: 12902045B

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T04CM02409
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2004 LLESNY1 WWM REVIEW Needs Review
06/01/2004 LLESNY1 FIRE REVIEW Needs Review
06/01/2004 LLESNY1 WATER REVIEW Needs Review
06/03/2004 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Approved
06/03/2004 GP 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
06/03/2004 TAMI ACHONG OUT TO CUSTOMER Completed