Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM02034
Parcel: 138170440

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM02034
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2004 Andrew Connor NPPO REVIEW Approved
08/20/2004 Loren Makus ENGINEERING REVIEW Denied Building plans may not be approved prior to site plan approval.
09/02/2004 Terry Stevens BUILDING-RESIDENTIAL REVIEW Approved
09/08/2004 ROBERT SHERRY PLUMBING-RESIDENTIAL REVIEW Denied 1. Confirm the manufacturer's required minimum static pressure for the water closet is 8 PSI. Reference Section 608.1, UPC 1994.
2. Limit the water velocity to less than 8 fps for the PVC and Copper piping. Reference Section A 6.1, UPC 1994; IAPMO IS 3-93, Section 610.0; and IAPMO IS 8-92, Section 610.1.
3. Provide upper terminal cleanouts on horizontal drainage pipe. Reference Section 707.4, UPC 1994.
09/08/2004 ROBERT SHERRY MECHANICAL-RESIDENTIAL REVIEW Approved
09/13/2004 DAN CASTRO ZONING REVIEW Denied Zoning may not approve the structural plans until the site plan has been approved by all sections and the building plans have been approved by all structural reviewers.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/17/2004 BETH GRANT OUT TO CUSTOMER Completed
09/17/2004 BETH GRANT REJECT SHELF Completed