Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM02034
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/19/2004 | Andrew Connor | NPPO | REVIEW | Approved | |
| 08/20/2004 | Loren Makus | ENGINEERING | REVIEW | Denied | Building plans may not be approved prior to site plan approval. |
| 09/02/2004 | Terry Stevens | BUILDING-RESIDENTIAL | REVIEW | Approved | |
| 09/08/2004 | ROBERT SHERRY | PLUMBING-RESIDENTIAL | REVIEW | Denied | 1. Confirm the manufacturer's required minimum static pressure for the water closet is 8 PSI. Reference Section 608.1, UPC 1994. 2. Limit the water velocity to less than 8 fps for the PVC and Copper piping. Reference Section A 6.1, UPC 1994; IAPMO IS 3-93, Section 610.0; and IAPMO IS 8-92, Section 610.1. 3. Provide upper terminal cleanouts on horizontal drainage pipe. Reference Section 707.4, UPC 1994. |
| 09/08/2004 | ROBERT SHERRY | MECHANICAL-RESIDENTIAL | REVIEW | Approved | |
| 09/13/2004 | DAN CASTRO | ZONING | REVIEW | Denied | Zoning may not approve the structural plans until the site plan has been approved by all sections and the building plans have been approved by all structural reviewers. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/17/2004 | BETH GRANT | OUT TO CUSTOMER | Completed |
| 09/17/2004 | BETH GRANT | REJECT SHELF | Completed |