Permit Number: T04CM02033
Parcel: 138170440

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM02033
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2004 ANDREW CONNOR NPPO REVIEW Approved
08/23/2004 DOUG WILLIAMS ENGINEERING REVIEW Denied Building plans may not be approved prior to site plan approval.
09/02/2004 Terry Stevens BUILDING-RESIDENTIAL REVIEW Approved
09/08/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/08/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Confirm the manufacturer's required minimum static pressure for the water closet is 8 PSI. Reference Section 608.1, UPC 1994.
2. Limit the water velocity to less than 8 fps for the PVC and Copper piping. Reference Section A 6.1, UPC 1994; IAPMO IS 3-93, Section 610.0; and IAPMO IS 8-92, Section 610.1.
3. Provide upper terminal cleanouts on horizontal drainage pipe. Reference Section 707.4, UPC 1994.
4. Provide cleanouts for the building sewer at intervals of no more than 100 feet and for aggregate changes of direction of greater than 135 degrees. Reference Section 719.1, UPC 1994.
5. Drawing C-3 indicates "back flow valves" have been added to the main building sewer prior to the HCS. Provide the rim elevation of the next upstream sanitary manhole and determine the need for a backwater valve and the placement of the valve per Section 710.1, UPC 1994.
09/13/2004 DAN CASTRO ZONING REVIEW Denied Zoning may not approve the structural plans until the site plan has been approved by all sections and the building plans have been approved by all structural reviewers.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/15/2004 TAMI ACHONG OUT TO CUSTOMER Completed
09/15/2004 TAMI ACHONG REJECT SHELF Completed