Permit Number: T04CM02033
Parcel: 138170440

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T04CM02033
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2004 DAN CASTRO ZONING REVIEW Approved
08/19/2004 ANDREW CONNOR NPPO REVIEW Approved
08/19/2004 ANDREW CONNOR LANDSCAPE REVIEW Approved
08/23/2004 DOUG WILLIAMS ENGINEERING REVIEW Denied The site and grading plan indicate proposed drainage concentrations across pedestrian circulation paths at the wheelchair ramps/landings along the eastern perimeter of the property. The plans must be revised to demonstrate conveyance of 100% of all 10-year flows under pedestrian/sidewalk areas, in accordance with Development Standards 2-08.2.4.1 E and 2-08.5.1 E.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/15/2004 TAMI ACHONG OUT TO CUSTOMER Completed
09/15/2004 TAMI ACHONG REJECT SHELF Completed