Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM01935
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/30/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 04/30/2004 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
| 05/03/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/03/2004 | NEAL SAUNDERS | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Electrical note plas E-1 shows four 15 HP fans will be removed from existing MCC-1, then tapping to hot side of MCC-1 to go outside of MCC and adding 2 60 amp cidisconnects outside of MCC unit. Please verify reason as to why new loads cannot be installed to MCC rather than tapping buss. Ray Majuta |
| 05/03/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 05/11/2004 | CAGUILA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 05/17/2004 | ROBERT SHERRY | WATER | REVIEW | Approved |