Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM01885
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/10/2005 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/29/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 12/29/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate the finished floor elevations shown on sheets C1.1, C2.1 (2520.28'), and P0 (2519.76'). 2. Show the location of the RPBP and indicate its size. Coordinate the size of the RPBP with sheets C1.1 and C2.1. 3. Sheet A-5 (Revision 1) calls for "5 4" roof drains w/ 8"x 8" overflow"; sheet A-7 still shows 5 6"x 6" scuppers; and your response letter notes that the architect will be providing 5 4" roof drains with 4" leaders. Please clarify what is being provided. Provide calculations to show that the specified scuppers, roof drains, or overflows are capable of handling the design rainfall. Reference Sections D3.1 and D3.2, UPC 1994. |
| 12/29/2004 | PATRICIA GEHLEN | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/12/2005 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 01/12/2005 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |