Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2005 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved
12/29/2004 PATRICIA GEHLEN ZONING REVIEW Approved
12/29/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the finished floor elevations shown on sheets C1.1, C2.1 (2520.28'), and P0 (2519.76').
2. Show the location of the RPBP and indicate its size. Coordinate the size of the RPBP with sheets C1.1 and C2.1.
3. Sheet A-5 (Revision 1) calls for "5 4" roof drains w/ 8"x 8" overflow"; sheet A-7 still shows 5 6"x 6" scuppers; and your response letter notes that the architect will be providing 5 4" roof drains with 4" leaders. Please clarify what is being provided. Provide calculations to show that the specified scuppers, roof drains, or overflows are capable of handling the design rainfall. Reference Sections D3.1 and D3.2, UPC 1994.
12/29/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/12/2005 TAMI ACHONG OUT TO CUSTOMER Completed
01/12/2005 ANGIE SHOFFSTALL REJECT SHELF Completed