Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM01885
Parcel: 13821030F

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM01885
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2005 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved
12/29/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
12/29/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the finished floor elevations shown on sheets C1.1, C2.1 (2520.28'), and P0 (2519.76').
2. Show the location of the RPBP and indicate its size. Coordinate the size of the RPBP with sheets C1.1 and C2.1.
3. Sheet A-5 (Revision 1) calls for "5 4" roof drains w/ 8"x 8" overflow"; sheet A-7 still shows 5 6"x 6" scuppers; and your response letter notes that the architect will be providing 5 4" roof drains with 4" leaders. Please clarify what is being provided. Provide calculations to show that the specified scuppers, roof drains, or overflows are capable of handling the design rainfall. Reference Sections D3.1 and D3.2, UPC 1994.
12/29/2004 PATRICIA GEHLEN ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/12/2005 TAMI ACHONG OUT TO CUSTOMER Completed
01/12/2005 ANGIE SHOFFSTALL REJECT SHELF Completed