Permit Number: T04CM01811
Parcel: 140292040

Review Status: Completed

Review Details: REVISION

Permit Number - T04CM01811
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/13/2004 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T04CM01811-r(12/09/04) .. 3675 E BRITTAINIA DRIVE .. DGL .. SHOP DRAWINGS FOR CANOPY : GUARDS AND HANDRAILS , METAL DECKING , FRAMING (COLUMNS AND BEAMS) .. 12/10/04 ..

S1. Revise 42" high guards to extend down stairways to the level at which the stair is not located more than 30 inches above grade below, per IBC Section 1003.2.12 , ref sections A and B on drawing E8, 33A on drawing 33, 34B on drawing 34.
S2. Revise guards to locate mid-rail at a height such that a 21" diameter sphere cannot pass through per IBC Section 1003.2.12 , ref Section 33A on drawing 33, 34A ,34B , 34C, 34D on drawing 34, Section A , Section B, Section C, Section D and Guardrail Splice Detail on drawing E8.
S3. Extend stair handrail at least 12" horizontally beyond the top riser per IBC Section 1003.3.11.5 , ref Section B and Section C on drawing E8, 33A and 33B on drawing 33.
S4. Detail embedment into concrete including materials IE. Sleeves, epoxy ETC.
S5. Justify edge distance by structural calculation to show conformance with IBC Section 1607.7.
S6. Provide documents including drawings with a minimum of 10 point font , ref drawing D1,notes.

Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111.