Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM01811
Parcel: 140292040

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM01811
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/24/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/29/2004 Doug Laakso BUILDING-COMMERCIAL REVIEW Denied .. T04CM01811 .. 3675 E BRITANNIA DRIVE .. DGL .. 6/29/04

2nd REVIEW ITEMS #1 - #11

1. See prior comment #4 , dispersed accessibile parking is required per IBC Section #1106 , revise site plan to show conformance.( 4. Provide site plan showing grades with spot elevations clearly showing the accessibile route conforms from the finish floor of the building to the public access locations , including ramps, landings, parking, etc. Provide tie of grade to established datum.)
2. See prior comment #5 , provide requested details and information on drawings. (5. Fully detail walls at SES including materials of construction, connections to structure above and below (w/fastener type, size, spacing/ number), fire listing on drawings for fire rating and details to conform with fire rating, ref drawing #A2.1 and A2.2.)
3. See prior comment #8 , provide required addressing or letter from Pima County Addressing approving addressing on elevations as shown on drawing #A3.1. (8. Provide addressing per Pima County Addressing Ordinance on South and East elevation.)
4. See prior comment #9 , provide continuous footing as required. (9. Provide continuous footing at line E-9 to 10.)
5. See prior comment #12 , provide required mechanical connection of tilt-up wall to foundation and document with calculations , ref IBC Sections 1604.8, 1609, 1614, 1616, 1906, 1908, 1910,1912, 1913, ACI 318-99 Chapter 14 ,etc. (12. Explain and justify opening extending to bottom of panel type 'E' on drawing # S-5.)
6. See prior comment #13 , drawing #A2.2 ,dated 4/15/04, in resubmitted set shows scissor lifts , please coordinate drawings. (13. Clarify dimensions for scissor lift detail 9/S6 , 1/A2.2.)
7. See prior comment #14, and provide required mechanical connection of tilt-up wall to foundation and document with calculations , ref IBC Sections 1604.8, 1609, 1614, 1616, 1906, 1908, 1910,1912, 1913, ACI 318-99 Chapter 14 ,etc. (14. Clarify how tilt-up walls conform to requirements of IBC, ref detail 11/S6.)
8. See prior comment #15 , detail 15/A1.2 does not exist and detail 5/A1.2 does not comply with calculations noted on resubmitted set drawing A1.2 dated 4/15/04, please coordinate drawings and calculations. (15. Provide foundation design and details for light poles ref detail 1/E3.)
9. See prior comment #21, dowels from tilt-up wall panel to floor slab required to be #4 @ 12" o.c. vs #4@ 48" o.c. per detail 5/S6 , please revise detail 5/S6 to conform. (21. Provide connection design in structural calculations for : beams, columns, joists, piping, tilt-up panels to ledger, tilt-up panels to adjacent panels and tilt-up panels to floor slab.)
10. See prior comment #22 , provide Inspection Program. (22. Provide inspection program conforming to Uniform Administrative Code - 1997 ed Sec 302.5.)
11. See prior comment #25 , anchorage to footings also required , provide required mechanical connection of tilt-up wall to foundation and document with calculations , ref IBC Sections 1604.8, 1609, 1614, 1616, 1906, 1908, 1910,1912, 1913, ACI 318-99 Chapter 14 ,etc .(25. Show where anchorage design per IBC Sec 1604.8 is provided for in structural calculations and on the drawings.)

Questions? Call Douglas Laakso, Structural Plans Examiner with City of Tucson - Development Services Department at (520) 791-5550 x 1111.
07/01/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
07/08/2004 DOUG WILLIAMS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/09/2004 BETH GRANT OUT TO CUSTOMER Completed
07/09/2004 ANGIE SHOFFSTALL REJECT SHELF Completed