Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM01811
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/16/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Show how the roof is capable of draining without ponding at columns 2, 2.5, 4, 4.5, 6, and 8. 2. Comment not addressed. Show the size and configuration of the downspouts referenced in the roof plan (detail 1/A2.3). 3. The rim elevation of the upstream sanitary manhole appears to be higher than the first floor elevation. Provide backwater valves per Section 710.1, UPC 1994. 4. Show the size and location of the reduced pressure backflow preventer assembly for the water service on the site drawing. Reference Section 103.2.3, UPC 1994. |
| 06/16/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The 06/14/04 revision to sheet A2.3 shows 17 rooftop units and the note to "see mechanical". Please provide mechanical drawings. |
| 06/17/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 06/21/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 06/22/2004 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 06/24/2004 | ASHOFFS1 | ZONING | REVIEW | Needs Review | |
| 06/24/2004 | ASHOFFS1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/24/2004 | BETH GRANT | OUT TO CUSTOMER | Completed |
| 06/24/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |