Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM01811
Parcel: 140292040

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM01811
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Show how the roof is capable of draining without ponding at columns 2, 2.5, 4, 4.5, 6, and 8.
2. Comment not addressed. Show the size and configuration of the downspouts referenced in the roof plan (detail 1/A2.3).
3. The rim elevation of the upstream sanitary manhole appears to be higher than the first floor elevation. Provide backwater valves per Section 710.1, UPC 1994.
4. Show the size and location of the reduced pressure backflow preventer assembly for the water service on the site drawing. Reference Section 103.2.3, UPC 1994.
06/16/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The 06/14/04 revision to sheet A2.3 shows 17 rooftop units and the note to "see mechanical". Please provide mechanical drawings.
06/17/2004 JIM EGAN FIRE REVIEW Approved
06/21/2004 GERRY KOZIOL WWM REVIEW Approved
06/22/2004 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Needs Review
06/24/2004 ASHOFFS1 ZONING REVIEW Needs Review
06/24/2004 ASHOFFS1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/24/2004 BETH GRANT OUT TO CUSTOMER Completed
06/24/2004 ANGIE SHOFFSTALL REJECT SHELF Completed