Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T04CM01490
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/19/2004 | GERRY KOZIOL | WWM | REVIEW | Denied | septic design must be submitted for review prior to issue |
| 05/05/2004 | DAVE WITT | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T04CM01490 5/5/04 4960 E. CALLE JABOLI PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. FOUNDATION PLANS: 1. THE MINIMUM FOOTING WIDTH OF THE FOOTING FOR A VENEERED WALL IS 19" PER TABLE R403.1 . 2. PROVIDE A LANDING OUTSIDE DOOR 110. SEE R312.1.2 . FLOOR PLANS: 1. PLEASE IDENTIFY THE ROOMS ADJACENT THE GARAGE AND THE ROOM BETWEEN THE LAUNDRY AND THE BATH. 2. THE BRACED WALL PANELS ADJACENT DOOR 112 APPEAR TO BE LESS THAN THE MINIMUM WIDTH MENTIONED IN R602.10.6 . 3. PLEASE DIMENSION THE OFF-SET IN THE BRACED WALL PANEL LINES ADJACENT DOOR 112. 4. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY ACCESSIBLE SPACE PER R807. STRUCTURAL PLANS: 1. JUSTIFY THE HEADER FOR A 8' AND 12' SPAN. 2. HOW IS THE RAFTER CONNECTION MADE AT THE RIDGE? PLEASE CONSIDER R802.3 . 3. SPECIFY LUMBER GRADE AND SPECIES. 4. PROVIDE MANUFACTURER'S TRUSS DATA SHEETS. DATA SHEETS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA. 5. THE 2X8 @ 24" O.C. APPEAR TO BE OVER SPANNED FOR HALF OF THE 30 FT WIDTH AT THE OVER FRAME ROOF. 6. SPECIFY AND DETAIL ALL OVER FRAMING. IF SOLID SHEATHING IS USED ON THE LOWER TRUSSES, PROVIDE MINIMUM OPENINGS OF 22" BY 30" FOR ACCESS AND VENTILATION INTO OVER FRAMED AREAS (>30 S.F.). IF SOLID SHEATHING IS NOT USED ON LOWER TRUSSES, PROVIDE DETAILS FOR BRACING OF TOP CHORD OF LOWER TRUSSES. ELEVATIONS: 1. PLEASE SPECIFY THE DIMENSIONS OF THE ATTIC VENTS. 2. SPECIFY THE ROOFING MATERIAL. SECTIONS - DETAILS - MISC. NOTES: 1. 8 / A-3 ; HOW DOES THE GYP BOARD ON THE CEILING COMPLY WITH TABLE R702.3.5 FOOTNOTE D? 2. 8 / A-3 ; HOW DO THE 4X6 @ 30" O.C. CONNECT TO THETRUSSES @ 24" O.C.? 3. 11 / A-3 ; HOW IS THE RAFTER CONNECTED TO THE PLATE? 4. PLEASE PROVIDE A DETAIL FOR THE VENEER ATTACHMENT TO THE WALL,SUPPORT AT THE BOTTOM, WEEP HOLES, FLASHING, LINTELS, WEATHER PROTECTION OF THE WALL SHEATHING, AIR SPACE (OR GROUT). SEE R703.7 . 5. WINDOW SCHEDULE / A-2.1 ; PLEASE SPEC SAFETY GLASS FOR WINDOW 102. PLUMBING PLANS: 1. WATER DEMAND CALCULATIONS / A-6 ; PLEASE CO-ORDINATE THE WATER FIXTURE UNITS WITH U.P.C. TABLE 6-3 . 2. PLEASE PROVIDE A WATER DISTRIBUTION PLAN. JUSTIFY, IF TAPPING THE EXISTING PIPING, THE SIZE BACK TO THE WATER METER. 3. NOTE ON PLANS THAT SHOWERS THAT HAVE INDIVIDUAL CONTROL VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE. MECHANICAL PLANS: 1. NOTE ON PLANS: MECHANICAL SHALL COMPLY WITH CHAPTERS 12 - 24 2000 IRC. 2. PLEASE SIZE THE SUPPLY AND RETURN AIR TRUNKS IN ACCORD WITH M1602 AND M1603. 3. SHOW EXHAUST FAN LOCATIONS FOR THE LAUNDRY ROOM IN LIEU OF OPERABLE WINDOWS, PER R303.3 ELECTRICAL PLANS: 1. NOTE ON PLANS: ELECTRICAL WORK SHALL COMPLY WITH CHAPTERS 33 - 42, 2000 IRC. 2. ON THE PLAN, PLEASE ASSIGN THE CIRCUITS TO THE ELECTRICAL DEVICES. IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 791-5550 EXT. 1110 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/05/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 05/05/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |