Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM01256
Parcel: 128010010

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM01256
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
03/17/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Use the fixture units from Tables 6-3 and 7-3, UPC 1994 for calculations and sizing.
2. Provide calculations to show that the water piping has been sized in accordance with Section 610.1, UPC 1994.
03/17/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
03/17/2004 ROBERT SHERRY WATER REVIEW Approved
03/17/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/19/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM01256 DENIED 3/19/04
1. Identify panel and circuit numbers for all new electrical loads.
2. Provide panel schedule.
3. Provide panel load calculations.
4. Specify conductor size and insulation type.
6. Specify conduit size and type.
03/29/2004 TACHONG1 WWM REVIEW Needs Review
03/29/2004 TACHONG1 FIRE REVIEW Needs Review
03/29/2004 TACHONG1 BUILDING-COMMERCIAL REVIEW Denied SEE COMMENTS ON APPLICATION.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/29/2004 TAMI ACHONG OUT TO CUSTOMER Completed