Permit Number: T04CM00757
Parcel: 133230880

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM00757
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM00757 DENIED 8/4/04
1. Panel feeder A shows (2) 700 MCMTHW Al. What size is neutral?
2. Panel A not braced for 20,000 AFC. Please address.
3. Provide WH disconnect per NEC 422 Part III.
4. It appears that Circuit "A-35" on Electrical Plan should read "A-33."
5. Put the symbol for the lights on Circuit A-33 on the Electrical Symbol Schedule, along with such lighting fixture description.
6. The 44.03 KVA on the high leg of Panel A is for that phase only, and as such shall be divided by 120V, not 240V.
7. Circuits A-6 and A-8, with 20A, single-pole CBs and #14 wire, will not power 3500W water heaters, which would draw over 29A.
8. Water heaters on plans do not coincide in phase with those indicated in the attached cut sheet. Please clarify.
08/04/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/04/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/16/2004 Raul Palma BUILDING-COMMERCIAL REVIEW Denied 1) Provide engineer`s stamp on structural portion of plans.