Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM00757
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/19/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the location of the water heater - it is noted as being above the restroom on sheet A2 and above the kitchen on sheet MP-1. 2. Provide access and working space for water heater. Reference Section 511.0, UPC 1994. |
| 03/19/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/19/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide calculations demonstrating adequate ventilation for the new conference room. Reference Section 403.3, IMC 2000. |
| 03/29/2004 | Raul Palma | BUILDING-COMMERCIAL | REVIEW | Denied | City of Tucson, Development Services BUILDING AND STRUCTURAL COMMENTS 1) Provide engineering calc`s for new roof structural members. 2) Provide engineering calc`s for ledger and anchor bolts. |
| 04/05/2004 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1.Provide info on waterfall pump(circuit,voltage,amperage,conductor size,etc.) 2.Indicate circuiting @ conference room lighting. 3 .A.C. unit "A" is fused at 45 amps with load of 52.5 FLA ? Please fuse accordingly. 4. Panel feeder "A" indicates 2#700 MCM THW conductors? This s/b a three wire system. 5. Provide the available fault current as well as the panels withstand rating for panel "A". 6. provide the exit lighting loads. |
| 04/06/2004 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/05/2004 | EGRANT1 | OUT TO CUSTOMER | Completed |
| 04/07/2004 | SUE REEVES | REJECT SHELF | Completed |