Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the location of the water heater - it is noted as being above the restroom on sheet A2 and above the kitchen on sheet MP-1.
2. Provide access and working space for water heater. Reference Section 511.0, UPC 1994.
03/19/2004 ROBERT SHERRY WATER REVIEW Approved
03/19/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide calculations demonstrating adequate ventilation for the new conference room. Reference Section 403.3, IMC 2000.
03/29/2004 Raul Palma BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS


1) Provide engineering calc`s for new roof structural members.
2) Provide engineering calc`s for ledger and anchor bolts.
04/05/2004 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.Provide info on waterfall pump(circuit,voltage,amperage,conductor size,etc.) 2.Indicate circuiting @ conference room lighting. 3 .A.C. unit "A" is fused at 45 amps with load of 52.5 FLA ? Please fuse accordingly. 4. Panel feeder "A" indicates 2#700 MCM THW conductors? This s/b a three wire system. 5. Provide the available fault current as well as the panels withstand rating for panel "A". 6. provide the exit lighting loads.
04/06/2004 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/05/2004 EGRANT1 OUT TO CUSTOMER Completed
04/07/2004 SUE REEVES REJECT SHELF Completed