Permit Number: T04CM00368
Parcel: 116272250

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T04CM00368
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2004 JIM EGAN FIRE REVIEW Denied 1. A minimum 20 feet wide, paved, fire apparatus access roadway must be provided and extended to within 150 feet of all portions of the exterior walls of the structure. An approved turnaround is required for dead-end fire access roadways.

2. Show location of nearest existing fire hydrant on plan.
05/25/2004 GERRY KOZIOL WWM REVIEW Approved
05/26/2004 DAVE MANN BUILDING-COMMERCIAL REVIEW Approv-Cond
06/04/2004 Loren Makus ENGINEERING REVIEW Approved
06/08/2004 Andrew Connor LANDSCAPE REVIEW Denied 1. Provide calculation for mitigation of native plants per Eagles View Landscape Concept Plan dated January 11,1993 or submit separate NPP plan per DS 2-15.0

2. Note: Fencing shall be required during construction for all undisturbed plans and natural desert areas per DS 2-6.0 Figure-1


3. Note: Prior to any site disturbance a pre-grading inspection is required. Inspections may be scheduled by calling the IVR system at (520) 740-6970, inspection #9015 or by calling the Landscape Field Representative directly at 791-5640 Ext. 1140.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/29/2004 DELMA ROBEY OUT TO CUSTOMER Completed