Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM00368
Parcel: 116272250

Review Status: Completed

Review Details: 3RD PARTY REVIEW-RESIDENTIAL

Permit Number - T04CM00368
Review Name: 3RD PARTY REVIEW-RESIDENTIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2004 DAN CASTRO ZONING REVIEW Approved
02/17/2004 EROSE1 WWM REVIEW Needs Review
02/17/2004 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet 1.1
1. Please provide the civil plan identified in the drawing index as Sheet 2.1.

Sheet 3.1
1. Specify dimensions for risers and tread depths at all interior and exterior stairs. Dimension stair widths and handrail heights. Ref. R314.

2. Clarify if the pool and pool barrier are by separate permit. No plans or design calculations have been provided for these elements and barrier requirements are not shown at the porch areas.

3. Revise seismic criteria to specify site class "C", design category "C" or delete.

Sheet 4.1
1. Provide the evaluation report numbers for the stucco system and stone veneer.

2. Provide details for the exterior guardrails. Ref. R316.

Sheet 5.1
1. Show the locations and dimensions of the attic openings. Ref. R807.

Sheet 6.1
1. Show the size, type and location of roof ventilation. Ref. R806.

2. Coordinate keynotes for the plan.

Sheet 8.1
1. The floor plan calls out manufactured fireplaces. Please clarify where the masonry fireplace detailed at 10/8.1 will be constructed.

STRUCTURAL COMMENTS
Sheet S1
1. Review special inspection requirements shown on this sheet and delete those that are not applicable to this project.

2. The design soil bearing specification of 2000psf is shown in the foundation notes. The design calculations assume a soil bearing pressure of 1500psf. Please revise.

3. Revise the rough carpentry nailing schedule note 5 to indicate the IBC as the governing code and Table 2304.9 as the nailing reference.

Sheet S2
1. Coordinate shearwall locations on the plan with the design calculations at lines 1, A and E.

2. Address the pool / powder shower condition on the foundation plan.

Sheet S3
1. Provide Sheet 4 of the design calculations. This sheet would be the key plan for the beam design.

Sheet S4
1. The design calculations for the cantilevered retaining wall use a soil bearing pressure of 2000psf. Revise to indicate 1500psf as shown in the design criteria.

PLUMBING COMMENTS
Sheet P1
1. Specify cross-connection control at irrigation stubout. Ref. UPC 603.

2. Revise cleanout size at 4" hcs line. Ref. UPC 707


Sheet P2
1. Include the second log lighter in the gas demand calculations. Ref. UPC 1217.

MECHANICAL COMMENTS-The mechanical portion has been reviewed and approved.

ELECTRICAL COMMENTS
Sheet E1
1. An additional gfci countertop receptacle is required along the south counter. Ref. E3801.4

Sheet E2
1. Switches to lighting are required at the exterior great room and pool / powder room. Ref. E3803.3.

ENERGY COMMENTS - The energy portion has been reviewed and approved.
02/17/2004 EROSE1 NPPO REVIEW Needs Review
02/17/2004 EROSE1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/17/2004 ELAINE ROSE OUT TO CUSTOMER Completed