Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T04CM00310
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/26/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Passed | |
| 01/26/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM00310 DENIED 1/26/04 1. Indicate panel and circuit number for new Gate Operator. 2. Provide a disconnect per NEC 430 Part J. 3. Load calculation is incorrect. (28,880)/(1.73)(208) = 80. |
| 03/04/2004 | DAN CASTRO | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/09/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |