Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM00310
Parcel: 11205278A

Address:
2401 E GLENN ST

Review Status: Completed

Review Details: OTHER

Permit Number - T04CM00310
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Passed
01/26/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM00310 DENIED 1/26/04
1. Indicate panel and circuit number for new Gate Operator.
2. Provide a disconnect per NEC 430 Part J.
3. Load calculation is incorrect. (28,880)/(1.73)(208) = 80.
03/04/2004 DAN CASTRO ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/09/2004 TAMI ACHONG OUT TO CUSTOMER Completed