Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2004 GERRY KOZIOL WWM REVIEW Approved
05/25/2004 Bruce Stevens BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS PROJECT #T04CM00213
05/26/2004 2648 N. Balboa Ave. #A

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.
SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, model energy and electrical. All code references are to the 2000 International Residential Code, 2000 International Energy Conservation Code, and Arizona State Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.
GENERAL REQUIREMENTS:
SECTIONS - DETAILS - MISC. NOTES:
1. On standard detail sheets, cross out all details that do not apply or are not being used. You are using an interior bearing footing detail that does not appear to apply to your building. An interior non-bearing wall section would be appropriate.
2. Detail non-bearing wall connection to wood trusses or ceiling joists.
3. Specify anchor bolt size and spacing for attic firewall attachment to masonry party wall.
MECHANICAL PLANS:
1. Note on plans: Mechanical shall comply with 2000 IRC chapters 18- 24.
2. Show size and location of return air grille. Supply and return air shall be sized per IRC sections M1602.2 and M1603.1. (heat pump / air conditioner - 6 sq. in. / 1000 BTU) (1ton cooling = 12,000 BTU)
ELECTRICAL PLANS:
1. Note on plan that all electrical work shall comply with 2000 IRC chapters 33 - 42.
2. Designate the location and circuit of all existing and new light fixtures, receptacles, and switches. Provide a panel schedule noting circuit number and size along with a general description.
3. Provide an exterior outlet at grade level located at both the front and back of the dwelling, per E3801.7. these outlets shall be GFCI protected per E3802.3.
4. Receptacle outlets shall be provided at each kitchen counter space wider than 12", and shall be installed so that no point along the wall line is more than 24" from a receptacle outlet, per E3801.4.1.
5. A receptacle outlet shall be provided adjacent to the basin in each bathroom, per E3801.6. Bathroom outlets shall be on a separate 20 AMP circuit with no other outlets, per E33603.4.
6. All receptacle outlets in bathrooms, kitchens, unfinished basements, garages or carports, at grade level and within 6' of a wet bar or kitchen sink shall have ground fault circuit interrupting protection. Note on the drawings at each outlet requiring such protection, per E3802.
7. Note that two or more 2O AMP small appliance circuits shall be provided to serve all receptacles outlets in the kitchen, breakfast room and dining room. Such circuits shall have no other outlets, per E3603.2 and E3801.3-4.5.
8. Show locations of smoke detectors per R317. Note that all smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup. When ceiling finish materials are removed in existing construction, existing bedrooms shall be in compliance. When ceiling finish materials are not removed, existing bedrooms shall be equipped with battery operated smoke detectors per R317.1.1.
If you have any questions, please contact your assigned plans examiner Bruce Stevens at 791-5550, extension 1174.
NOTE: As of 2-02-01 the City of Tucson has adopted the 2000 IRC with the exception of the plumbing portion which has been replaced with the Arizona state plumbing code. All model plans shall reference these codes.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/28/2004 EGRANT1 OUT TO CUSTOMER Completed
05/27/2004 ANGIE SHOFFSTALL REJECT SHELF Completed