Permit Number: T04BU03045
Parcel: 13816024D

Address:
335 E ELVIRA RD

Review Status: Completed

Review Details: GRADING

Permit Number - T04BU03045
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2005 Andrew Connor NPPO REVIEW Denied 1. Include in preserve in place calculations on landscape plan Prosopis velutina #26 indicated in NPP inventory and provide the ultimate locations of Prosopis velutina #1 identified as transplant on site and subsequent mitigation tree.

2. Site plan approval is necessary to continue review.
01/20/2005 Doug Williams ENGINEERING REVIEW Denied SUBJECT: Site/grading review - 335 E. Elvira Rd.
REVIEWER: Doug Williams
DATE: 21 January 2005
ACTIVITY NUMBERS: T04OT02511/T04BU03045

Engineering Division has reviewed the Subject site and Grading plans. Approval of the grading plan is not recommended at this time. Please provide a plan addressing the following comments:

1. Demonstrate containment of runoff in water harvesting areas on the east and west perimeters, and in the southwest corner of the site, meeting the 6" minimum depth for the water harvesting areas indicated. Elevations provided indicate straight grades to the northern portion of the site, without containment. Terracing/berming at periodic intervals (at contours provided), with proposed finish grades indicated, may sufficiently demonstrate containment in these areas (Sheets 3/4)
2. See "blueline" mark-ups on sheets 3 and 4 to address all other concerns/comments for grading plan approval.

An over-the-counter review may be scheduled with me upon addressing of all items indicated. Please contact me at 791-5550 ext. 1189, or via email at Doug.Williams@tucsonaz.gov to schedule an appointment, or if you have any questions. Assure "blueline" mark-ups are provided/available at the time an appointment is scheduled to occur.

Douglas Williams
Sr. Engineering Associate
Engineering Divsion
Development Services Department
01/22/2005 PETER MCLAUGHLIN ZONING REVIEW Denied Engineering approval required prior to zoning apprvl.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/31/2005 BETH GRANT OUT TO CUSTOMER Completed
01/31/2005 ANGIE SHOFFSTALL REJECT SHELF Completed