Permit Number: T04BU02156
Parcel: 138170370

Address:
475 E ELVADO RD

Review Status: Completed

Review Details: GRADING

Permit Number - T04BU02156
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2004 DAVID RIVERA ZONING REVIEW Denied Zoning will approve the grading plan once the Engineering and Landscape Sections have reviewed and approved the plan.
10/05/2004 LOREN MAKUS ENGINEERING REVIEW Denied DATE: October 5, 2004
TO: Steve Whillier, Conestoga-Rovers and
SUBJECT: Site Plan: TIAA Superfund Site
REVIEWER: Loren Makus
ACTIVITY NUMBER: T04CM03976, T04BU02516 and T04OT01737

SUMMARY: The Site Plan and Grading Plan were reviewed by Development Services Department, Engineering Division on September 22, 2004. This review is only for the project parcels along Elvado Road, outside of the Tucson International Airport. The portion of the project within the Airport was reviewed for floodplain issues only. The Site Plan and Grading Plan were not approved for the Elvado Road parcels. Please address the following comments.


1. Clearly show the existing and proposed drainage patterns on the Elvado parcels. The TIA master drainage report and the City of Tucson TSMS study indicate that there is a significant discharge through the culverts under Nogales Highway. Label the discharge quantity on the site/grading plan. Discuss the disposition of the discharge in a drainage statement or drainage report.
2. Determine the 100-year water surface elevation and the extent of the City of Tucson floodplain for the discharge. Provide the supporting calculations in the drainage statement/report.
3. In a note, list the area to be graded. If a total area to be disturbed exceeds 1 acre for all areas, a stormwater pollution prevention plan is required.
4. Provide details showing transition from the fill area to natural grade. Show that the toes of all fill slopes will be set back at least two feet from the property line.
5. Show sight visibilty triangles for the intersection of Nogales Highway and Elvado Road and for the access roads and Elvado Road.
Revise the Site Plan, to address all of these comments and resubmit two copies of each for review. Include a letter explaining how each comment has been addressed.
Loren Makus, E.I.T.
Senior Engineering Associate
Engineering Division
Development Services
10/06/2004 Andrew Connor NPPO REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
12/07/2004 LISA LESNY OUT TO CUSTOMER Completed
12/07/2004 ANGIE SHOFFSTALL REJECT SHELF Completed