Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T03CM05839
Parcel: 128010010

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05839
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Approved
01/02/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/02/2004 ROBERT SHERRY WATER REVIEW Approved
01/09/2004 Martin Haeberle BUILDING-COMMERCIAL REVIEW Approved
01/13/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

1. Panel B MCB appears to be overloaded. For example, Phase C at 7.7 KVA would carry 64A, even before considering continuous load. This exceeds the 50 CB capacity.
2. Feeder to Panel B, #6, ampacity 65A per the 75C column of Table 310-16, also appears overloaded.
3. The ground in the feeder to Panel B, and the GEC for the transformer, per Table 250-66, should be no smaller than #8.
4. Please note that the transformer KVA load would be the same as that for Panel B.
5. Fault calculations have parameters which did not come out in the printout. Please correct.
01/14/2004 GERRY KOZIOL WWM REVIEW Approved
12/23/2003 JIM EGAN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/20/2004 LISA LESNY OUT TO CUSTOMER Completed
01/14/2004 ANGIE SHOFFSTALL REJECT SHELF Completed