Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T03CM05695
Review Name: REVISION
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/14/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The Appeal to the Building Official allowed the ventilation requirements for this project to be calculated using ASHRAE Standard 62-2001 (Rev. N) in lieu of Section 403, IMC 2000, with the condition that "The occupant density used for calculations must be at least equal to the default occupant density". Note 1 of sheet M1.0 violates the conditions of the approved appeal by reducing the occupancy to less than the default occupancy shown in Table 6.1 of ASHRAE Standard 62-2001 (Rev. N). 2. Provide information on the sequence of operation for the restroom exhaust fans and the DX fan coils serving the restrooms to show that recirculation of the air from the restrooms will not occur. Reference Section 403.2.1, IMC 2000. 3. Provide listing information for the specified variable air volume terminal VVT-1. Reference Section 106.3.1, IMC 2000. 4. Clarify the relationship of the OSA duct (Keynote #7, M1.2) with the 12"x 12" duct that appears to supply air to the women's restroom on the first floor. 5. Provide smoke detectors in the return air duct, upstream of any outside air connections, for all air distribution systems with a capacity greater than 2,000 CFM. Reference Section 606.1, IMC. 6. Clarify the location of the details and sections called out on sheets M1.1, M1.2, and M1.3. Reference Section 106.3.1, IMC 2000. |
03/16/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
04/07/2005 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | Provide discussion of wood roof truss connection details including bearing in structural design calculations for this revision. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/12/2005 | DELMA ROBEY | OUT TO CUSTOMER | Completed |