Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T03CM05695
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/10/2004 | Jim Egan | FIRE | REVIEW | Approved | |
| 09/14/2004 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how the ventilation calculations for fan coils serving multiple zones conform to the requirements of ASHRAE 62-2001, Sections 6.2.2 and 6.2.4 (single-zone and recirculating multiple zone systems). 2. Show how the condensate drains on the fan coil units are to be routed and terminated. Reference Section 307.2.3, IMC 2000. |
| 09/16/2004 | Robert Suba | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/20/2004 | BETH GRANT | OUT TO CUSTOMER | Completed |
| 10/20/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |