Permit Number: T03CM05695
Parcel: 117120340

Address:
17 W CONGRESS ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM05695
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Approved
03/19/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/05/2004 GERRY KOZIOL WWM REVIEW Denied Needs WW design review of basement lift station - Robert Buecher, Pioneer Bldg, 4th floor, 100 N. Stone, 617-8206
04/09/2004 Doug Laakso BUILDING-COMMERCIAL REVIEW Denied .. T03CM05695 .. 17 W CONGRESS ST .. DGL .. 4/14/04 ..
.. THIRD REVIEW COMMENTS - #1 THROUGH #7 ..

1. See prior comment #1.Clarify Legal Description , This issue will not stop permitting process per discussion with Dave Mann COT- Building Official but will need to be resolved prior to issuance of Certificate of Occupancy.
2. See prior comment #2. Address Special Inspection items listed individually per Uniform Administrative Code Sec 302.5, provide required information in your Inspection Program.
3. See prior comment #6, correct hourly designations at door 201a and 201b on Drawing A1.3 from 2.5 hours to 3 hours.
4. See prior comment #8. Explain how fire-rating is accomplished by detail , if justification is a fire listing from out side of tables in IBC Chapter 7, provide a copy of the fire listing on the drawings, as well as your detail showing how to construct this assembly. Drawing A1.1 does not indicate door relocation, please clarify.
5. See prior comment #10. Provide detail for fire-rating in this location, beam to roof deck at wall section 4/A4.1.
6. See prior comment #14. Submit Building Permit application/s and backup documents including Official Address Slip/s from Pima County Addressing, Code Review Checklist, Project Valuation applicable to individual Building Permits for locations where work is being done.
7. See prior comment #18. Wall type F still references UL, on Drawing A7.4 Note #4.1still refers to cmu 8x8x16, please clarify w/detail.
Questions ? Please call Douglas Laakso, Structural Plans Examiner COT-DSD, at (520) 791-5550 x 1111.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/15/2004 CINDY AGUILAR OUT TO CUSTOMER Completed
04/15/2004 ANGIE SHOFFSTALL REJECT SHELF Completed