Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM05695
Parcel: 117120340

Address:
17 W CONGRESS ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM05695
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Reconcile the quantities of plumbing fixtures shown in the Plumbing Fixture Schedule with the number of fixtures and type of fixtures shown on the plans. (e.g. P3, P4, FS1, FS2, FD3, and FD4). Reference Section 103.2.3, UPC 1994.
2. Revise the water pressure calculations for each meter to correspond to the actual number of fixtures being served, the total lift for each system (e.g. 31-feet for Congress St.), and the developed length for each system. Revise the pipe sizing as required. Reference Section 610.1, UPC 1994.
3. Show vent for grease trap on riser diagram 1/P2.3 (this is not the vent for the directly connected compartments of the 3-compartment sink). Reference Section 103.2.3, UPC 1994.
4. Show that the gas train for the emergency generator complies with the requirements of NFPA 37. Reference Section 915.2, IMC 2000.
5. Relocate FS1 located in alcove of room 017 to be readily accessible for cleaning and inspection. Reference Section 804.1, UPC 1994.
01/28/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The ventilation rate for rooms 201 and 202 is more appropriately identified as "Theater - Lobby" with an occupant load of 150 people per 1000 square feet and 20 CFM per person. Reference Section 403.3, IMC 2000.
2. Show how the overflow drains on the fan coil units (Note 3, Fan Coil Schedule, M3.0) are to be routed and terminated. Reference Section 307.2.3, IMC 2000.
02/12/2004 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T03CM05695 .. 17 W. CONGRESS ST .. DGL .. 2/12/04 ..
.. COMMENTS #1 to #18, ( Prior Comments dated 1/5/04 ).
S1. Clarify site as one lot, eliminate property lines by owner/s
combining lots (legally) into a single lot, include copy of revised legal including easements and revise drawings to conform. See Prior Comment #1. This review is based on a combination of these lots and VOID if not combined. ( 17 w Congress St, 27 w Congress St, 33 w Congress St, 32 n Church Av, 38 n Church Av and unaddressed parcels used for
yard and exits for the Fox Theater).
S2. See Prior Comment #3. See Uniform Administrative Code Sec 302.5 and comply, as this is not the same as sections referred to in response.
S3. See Prior Comment #4. Stamp for Special Inspection will be placed on Approved Drawings, and may include additional inspection requirements.
14. Epoxy injection.
S4. See Prior Comment #10. Provide cross-section through lavatory to show knee and toe space requirement is provided for.
S5. Shop drawing stamp will be placed on Approved Drawings with a listing of required submittals, including prior listed items and may list additional items:
9. Ejector pit
10. Orchestra lift
11. Roff hatches
12. Guards
13. Structural steel
14. Door Hardware
15. Orchestra lift pit /walls/slab and footings.
S6. Provide 3-hour fire-rated opening protective in 3-hour fire-rated wall per IBC Sec 714, ref 1/a1.3 and door schedule on drawing A7.1, doors 102b, 201a, 201b.
S7. Clarify yard exit lighting and signage per IBC Sec 1005 and 1006.
S8. Provide infill details for opening at storage/bathroom, ref dwg A1.1, also provide landing at each side of storage exit door per IBC Sec 1003 w/ stair and railing.
S9. Clarify exterior footings extend 1'6" below lowest adjacent grade to bottom of footing, ref dwg 104/S4.0, 105/S4.0, 1/A4.2.
S10. Clarify two-hour wall fire-rating extending from beam to roof deck at wall section 4/A4.1.
S11. Justify/explain use of roll-up grille at door 102b, ref dwg a1.9 and door schedule A7.1.
S12. Where is location of safety glazing indicated?
S13. Remove/delete reference to "PREIMINARY DESIGN DEVELOPMENT" S2.0, S2.1, S2.2 below sheet number on title block.
S14. Building Permit required for work at 33 w Congress St and 32 n Church Av, per drawings, provide valuations for each Permit.
S15. Clarify fire protection at wall and structural columns, ref 4/A4.1, S3.0, 232/S5.2, 233/S5.2.
S16. Detail 260/S5.5, S3.0 extend lintel tie 24" beyond opening, per IBC Sec 2106.
S17. Clarify fire-rating at 8'0" opening for structural support, three-hour wall, ref dwg A1.3, door 201a, per IBC Sec 713.
S18. Clarify fire-rated detail at NOTE #4.1 on drawing A1.2, Stage Right Exit Passsage, also show construction detail.
Questions, Please call, Douglas Laakso, COT- Stuctural Plans Examiner at DSD (520) 791-5550 x 1111.
02/20/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
02/24/2004 GERRY KOZIOL WWM REVIEW Denied Needs WW design review of basement lift station. Robert Buecher - Pioneer Bldg, 4th Floor, 100 N. Stone 617-8206
03/23/2004 RANDY SCHULER HISTORIC REVIEW Approved
03/29/2004 RANDY SCHULER DRB REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/25/2004 CINDY AGUILAR OUT TO CUSTOMER Completed
02/25/2004 ANGIE SHOFFSTALL REJECT SHELF Completed