Permit Number: T03CM05695
Parcel: 117120340

Address:
17 W CONGRESS ST

Review Status: Completed

Review Details: REVISION - - 4TH

Permit Number - T03CM05695
Review Name: REVISION - - 4TH
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/30/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The pressure and flow data for the pipe organ provided by the architect (2800 CFM @ 1 PSIG) exceeds the rating of the fire damper for dynamic closure. Revise the design for the protection of the 14" duct penetrations as required to accommodate the actual operating conditions.
03/30/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the size of the water piping in Detail 4/P2.2 and Detail 2/P2.3 to correspond to sizes based on the calculations for Congress Street piping.
2. The cleanouts located downstream of the backwater valves shown on detail 1/P2.2 appear to be in violation of Section 707.6, UPC 1994.
3. Coordinate detail 3/P2.2 with the plumbing plan (i.e. what is fixture P2?).
4. Fixture K-34, located at the balcony level, requires a trap for the directly connected sink compartments. Reference Section 1011.8, UPC 1994 (currently approved grease traps do not have the required trap depth due to the presence of an air relief).
5. Commercial sinks such as K-34 require a 2"waste, not 1-1/2". Reference Table 7-3, UPC 1994.
04/11/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
04/11/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1. Provide construction details for installation of rigid insulation and stucco at equipment platform, ref drawing A1.0b, delta #3, including materials of construction and fastening to structure.
S2. Provide construction details for delta #10, ref drawing A1.2, including materials of construction and fastening to comply with fire-rating and connection to structure.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/14/2006 ADRIANNE OLIVO OUT TO CUSTOMER Completed
04/14/2006 SUE REEVES REJECT SHELF Approved