Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T03CM05695
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/01/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The pressure and flow data for the pipe organ provided by the architect (2800 CFM @ 1 PSIG) exceeds the rating of the fire damper for dynamic closure. Revise the design for the protection of the 14" duct penetrations as required to accomodate the actual operating conditions. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/13/2006 | SUE REEVES | OUT TO CUSTOMER | Completed |
03/13/2006 | SUE REEVES | REJECT SHELF | Completed |