Permit Number: T03CM05695
Parcel: 117120340

Address:
17 W CONGRESS ST

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T03CM05695
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/01/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The pressure and flow data for the pipe organ provided by the architect (2800 CFM @ 1 PSIG) exceeds the rating of the fire damper for dynamic closure. Revise the design for the protection of the 14" duct penetrations as required to accomodate the actual operating conditions.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/13/2006 SUE REEVES OUT TO CUSTOMER Completed
03/13/2006 SUE REEVES REJECT SHELF Completed