Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T03CM05505
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/06/2004 | Bruce Stevens | BUILDING-RESIDENTIAL | REVIEW | Approved | |
| 01/08/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 12/26/2003 | Patricia Gilbert | ENGINEERING | REVIEW | Denied | The Hydrology Report specifies that the minimum finish floor elevation must be 2465.3 NGVD-29. This must be specified on the Site Plan. Sheet 2 specifies the FFE as 0'-00". This is incorrect. The correct FFE must be shown on the plan. Please note that the as-built finish floor elevation must be certified by a Registered Land Surveyor on the form provided with the Flood Use Permit providing proof that the floor was poured to the correct elevation. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/08/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 01/08/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |