Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM05445
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/09/2004 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 03/09/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The water calculations provided do not correspond to the plans with regard to the developed length from the connection to the existing water line to the two new buildings. Revise the calculations as required and revise the pipe sizes as needed. Reference Section 610.1, UPC 1994. 2. Clarify how the hot water piping was sized: Section 610.12 or Section 610.13, UPC 1994. 3. Include the demand for the water supply outlet for the evaporative cooler located on building 5 and revise the required lift in the pressure calculations. Coordinate the water requirements for the evaporative cooler installation with the mechanical - detail 8/M2 shows a hose bibb being installed with the cooler. Reference Section 610.1, UPC 1994. |
| 03/19/2004 | Martin Haeberle | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/24/2004 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/26/2004 | EGRANT1 | OUT TO CUSTOMER | Completed |
| 03/25/2004 | SUE REEVES | REJECT SHELF | Completed |