Permit Number: T03CM05445
Parcel: 136070060

Address:
9252 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM05445
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/09/2004 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Approved
03/09/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The water calculations provided do not correspond to the plans with regard to the developed length from the connection to the existing water line to the two new buildings. Revise the calculations as required and revise the pipe sizes as needed. Reference Section 610.1, UPC 1994.
2. Clarify how the hot water piping was sized: Section 610.12 or Section 610.13, UPC 1994.
3. Include the demand for the water supply outlet for the evaporative cooler located on building 5 and revise the required lift in the pressure calculations. Coordinate the water requirements for the evaporative cooler installation with the mechanical - detail 8/M2 shows a hose bibb being installed with the cooler. Reference Section 610.1, UPC 1994.
03/19/2004 Martin Haeberle BUILDING-COMMERCIAL REVIEW Approved
03/24/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/26/2004 EGRANT1 OUT TO CUSTOMER Completed
03/25/2004 SUE REEVES REJECT SHELF Completed