| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/28/2004 | JIM EGAN | FIRE | REVIEW | Approved | 1. Type 1 exhaust hood and fire suppression system required for kitchen ranges. See 2000 IFC Sec. 609.2 and 2001 NFPA-96 Sec. 1.1.4. |
| 02/04/2004 | Martin Haeberle | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide details and structural calculations for installation of the required Type 1 hood required by the Fire Department and mechanical plans examiner. |
| 02/05/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The specified icemaker requires a reduced pressure backflow preventer, not a double check valve. Separate the icemaker supply from the other three appliances. Reference Section 603.0, UPC 1994. Note: the icemaker will be the fixture with the greatest pressure requirement: 20 PSI plus the pressure drop of the RPBP. 2. The plans indicate that the CW supplies to the two new buildings are tapping into the CW supply to the existing three buildings. Provide calculations to show that the existing piping and water meter can accommodate the added demand. Reference Section 610.1, UPC 1994. 3. Include the demand for the four water supply outlets (located in the kitchen of building 5) and the hot water demand for building 4 in the demand calculations for building 5. Reference Section 610.1, UPC 1994. 4. Revise the location of the HW shut off valves for the entrance to building 4 so they are accessible at all times. Reference Section 605.3, UPC 1994. |
| 02/05/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | A Type I Hood is required over the ranges in the kitchen. A range is a medium-temperature heat-processing appliance (Section 507.13.3, IMC 2000) and cannot be considered as only a "warming" appliance. Reference Section 507.2.2, IMC 2000. |
| 02/12/2004 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Approved |