Permit Number: T03CM05074
Parcel: 128010010

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05074
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/23/2003 LOREN MAKUS ENGINEERING REVIEW Approved
10/23/2003 MICHAEL ST. PAUL ZONING REVIEW Approved
10/29/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/29/2003 ANY BUILDING-COMMERCIAL REVIEW Passed
10/29/2003 ROBERT SHERRY WATER REVIEW Approved
10/29/2003 JIM EGAN FIRE REVIEW Approved
10/29/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/07/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved DENIED 10/29/03 T03CM05074
1. Sheet E1, Keynotes 6, 9, & 5. Per NEc 400-8, flexible cords and cables shall not be used where concealed behind dropped ceilings.
2. Panel B Circuit 21 is for MW & Refridgerator per Keynote 10, but for Show Window Lighting per Panel Schedule. Please clarify.
3. Sheet E3 correct lighting demand factor to 1.25. Certain of the branch circuits, such as 5, 9, 11, & 17, appear to be between the 100% and 125% loading. This could make a difference in the primary loading of the 30 KVA X'FMR, with a rated primary current of 36 amps.
11/07/2003 GERRY KOZIOL WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/07/2003 TAMI ACHONG OUT TO CUSTOMER Completed