Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/23/2003 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
10/23/2003 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
10/29/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
10/29/2003 | ANY | BUILDING-COMMERCIAL | REVIEW | Passed | |
10/29/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/29/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
10/29/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
11/07/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | DENIED 10/29/03 T03CM05074 1. Sheet E1, Keynotes 6, 9, & 5. Per NEc 400-8, flexible cords and cables shall not be used where concealed behind dropped ceilings. 2. Panel B Circuit 21 is for MW & Refridgerator per Keynote 10, but for Show Window Lighting per Panel Schedule. Please clarify. 3. Sheet E3 correct lighting demand factor to 1.25. Certain of the branch circuits, such as 5, 9, 11, & 17, appear to be between the 100% and 125% loading. This could make a difference in the primary loading of the 30 KVA X'FMR, with a rated primary current of 36 amps. |
11/07/2003 | GERRY KOZIOL | WWM | REVIEW | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/07/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |