Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM05048
Parcel: 11205095B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM05048
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2004 Neil Saunders BUILDING-RESIDENTIAL REVIEW Denied Plan Check Comments T04CM05048
Ray Clark

General Requirements

1. All corrections shall be made on the original tracings and two new sets of prints or (1) sepia and (1) blue line shall be returned.
2. Pen or Pencil corrections on final prints will not be acceptable. To avoid delays ensure that all corrections have been made, are complete and have been coordinated on all applicable details and notes.
3. List square footage on the plan.

Site Plan

1. Provide dimensions from applicable structure to property lines.
2. Indicate location of gas, water, electric and sewer lines on the property.

Foundation Plans

1. Landing at front door is required. Minimum 3' width, 6" on each side of door and it must slope away from the house.

Structural Plans

1. Detail the barge rafter and how it will attach to the north and south non-bearing wall. H2.5 or A35 on alternating studs.
2. Indicate exterior materials on all details.
3. Blocking for roof edge nailing is required to complete shear load path for roof diaphragm. Indicate on detail 1/W2.

Elevations

1. Provide attic ventilation calculations in compliance with R806.2 unless R-38 will be used.

Plumbing Plans

1. Note and specify that shower enclosures shall have a minimum finished interior of 1024 square inches and shall be capable of encompassing a minimum 30" circle per UPC sec 410.
2. Provide note regarding penetrations in fire wall on plumbing plans and electrical plans.
3. Lavatories and sinks cannot be on the same tree in a fire wall. The waste plumbing of these fixtures must be offset from each other.
4. Water heater must be put in an enclosure, Show this on the plan. Show pressure and temperature relief lines exiting the water heater enclosure.

Electrical Plans

1. Note circuit number on the plan view of each electrical fixture.

MEC

1. Provide MEC calculations per the 1998 IECC, or comply with IRC chapter 11.

ANY QUESTIONS PLEASE CONTACT NEIL SAUNDERS @791-5550 x2208
12/12/2003 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/06/2004 EGRANT1 OUT TO CUSTOMER Completed
02/06/2004 ANGIE SHOFFSTALL REJECT SHELF Completed