Permit Number: T03CM04686
Parcel: 141148180

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM04686
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2003 JIM EGAN FIRE REVIEW Approved
09/29/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise fixture unit calculation (P1) to include all of the fixtures shown on the plans (P1) and revise the fixture units to correspond to Tables 6-3 and 7-3, UPC 1994.
2. Provide flow control device for fixture connected to grease trap. Reference Section 1011.3, UPC 1994.
3. Revise waste isometric to agree with plumbing plans. (P2 shown as direct connection on isometric.)
4. Dishwasher must have an indirect waste. Reference Section 801.2, UPC 1994.
5. Provide size of existing water meter, RPBP, developed length, and total number of fixture units connected to the existing 2" CW line. Reference Section 610.1, UPC 1994.
6. Gas piping to be installed per UPC 1994.
7. Provide combustion and relief air for the water heater. Reference Section 507.3, UPC 1994.
8. Provide complete descriptions of plumbing fixtures. Reference Section 401, UPC 1994.
9. Provide information for water connection and drainage of make-up air unit.
09/29/2003 PATRICIA GILBERT ENGINEERING REVIEW Approved
09/29/2003 ROBERT SHERRY WATER REVIEW Approved
09/29/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide flue for water heater.
2. Provide balancing data to show how required amount of outside air is being introduced into the restaurant.
3. Provide Type 2 hood for dishwasher.
4. Provide size and balancing data for Type 1 exhaust hood.
5. Clarify designation for make-up air unit. E8 or EV-1?
6. Provide operating data for make up air unit (CFM, power required). Coordinate with electrical.
10/15/2003 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review
10/15/2003 DROBEY1 WWM REVIEW Needs Review
10/15/2003 DROBEY1 ZONING REVIEW Needs Review
10/15/2003 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review