Permit Number: T03CM04472
Parcel: 14027041A

Address:
6151 S TUCSON BL

Review Status: Completed

Review Details: SITE

Permit Number - T03CM04472
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/25/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
05/26/2004 PETER MCLAUGHLIN HANDICAP-SITE REVIEW Approved
06/04/2004 Jim Egan FIRE REVIEW Approved
06/10/2004 JOE LINVILLE NPPO REVIEW Denied Show the drainageway on the NPP. Show grading limits. Given the proximity of phase 1 improvements to PV22, revise the plans as necessary.
06/10/2004 Joseph Linville LANDSCAPE REVIEW Denied 1) Revise the landscape and native plant preservation plans to identify a limit of disturbance between phases 1 and 2.
Indicate site preservation fencing per DS 2-06 Figure 1at the disturbance limit on the native plant preservation plan.

2) Revise the landscape plan to include a provision for a seed mix or alternative dust control treatment for the proposed drainage way and other disturbed portions of the Phase II area. Show the proposed drainageway on the landscape and NPP plans.
06/21/2004 Loren Makus ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/29/2004 CINDY AGUILAR OUT TO CUSTOMER Completed
06/29/2004 ANGIE SHOFFSTALL REJECT SHELF Completed