Permit Number: T03CM04472
Parcel: 14027041A

Address:
6151 S TUCSON BL

Review Status: Completed

Review Details: SITE

Permit Number - T03CM04472
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2004 PETER MCLAUGHLIN HANDICAP-SITE REVIEW Approved
01/02/2004 PETER MCLAUGHLIN ZONING REVIEW Denied SITE PLAN TRANSMITTAL

TO: Acorn Associates Architecture Ltd.
4400 E. Broadway Blvd.
Tucson, AZ 85711
(520) 977-7187

FROM: Peter McLaughlin
Senior Planner
Development Services Dept.

FOR: Patricia Gehlen
Principal Planner
Development Services Dept.

PROJECT:
T02CM04472
Solar Industries
6151 S. Tucson Blvd
Site Plan Review (2nd review)

TRANSMITTAL: January 2, 2004


COMMENTS: The following items must be revised on or added to the site plan:

1. The Assessors Record maps indicate that the project site is made up of two lots. The lots must be combined prior to site plan approval. Provide copies of Assessors tax combo form and recorded covenant.
DS 2-02

2. Specify in the development data setback notes that the required MS&R building setback is dimensioned from the back of future curb location.
LUC 3.2.6.5

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.
01/06/2004 Joseph Linville LANDSCAPE REVIEW Approved
01/06/2004 JOE LINVILLE NPPO REVIEW Approved
12/30/2003 Loren Makus ENGINEERING REVIEW Denied SUBJECT: Solar Industries
REVIEWER: Loren Makus
DATE: 2 January, 2004
ACTIVITY NUMBER: T03CM04472
T15S, R14E, Section 8
SUMMARY: Engineering Division has reviewed the drainage Report, Stormwater Pollution Prevention Plan, Grading and Site Plans. Approval of the Site Plan may not occur prior to drainage report approval, and is not recommended at this time. Address the following comments in your re-submittal:
SITE and GRADING PLAN:
1. As previously commented, provide retention/detention basin details with elevations and dimensions fully labelled. The detail should be provided on the grading plan and in the drainage report.
2. The site and grading plans show retention/detention facilities within the right-of-way along Bilby Road. Contact the City of Tucson Department of Transportation Real Estate Division at (520) 791-4181 to obtain a Temporary Revocable Easement for private use of the Right-of-Way.
DRAINAGE REPORT
3. Provide retention/detention basin details with elevations and dimensions fully labeled, in the report (SMDDFM, sec. 2.3.1.6 A 4 a, d & e);
Please address all of the above comments. Resubmittal shall include a revised site and grading plan, drainage report, and should also include a completed grading permit application, SWPPP's and required accompanying documents. If you have any questions, I can be reached at 791-5550, extension 1161 or lmakus1@ci.tucson.az.us.
Loren Makus
Engineering Division
Development Services Department

Final Status

Task End Date Reviewer's Name Type of Review Description
02/03/2004 CINDY AGUILAR OUT TO CUSTOMER Completed
01/07/2004 ANGIE SHOFFSTALL REJECT SHELF Completed