Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T03CM03908
Parcel: 13315305A

Review Status: Completed

Review Details: REVISION - WALK THRU

Permit Number - T03CM03908
Review Name: REVISION - WALK THRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/11/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the dishwasher drain from direct to indirect waste.
2. Route the rinse sink to the grease trap.
3. Provide flow control devices for the rinse sink and the 2-compartment sink. The flow control devices shall be readily accessible.
4. Provide a terminal cleanout for the floor sink located under the steam tables. (All fixtures having a horizontal drain, 5 feet or longer, require a cleanout. Sinks and urinals require a cleanout if they have any horizontal drain piping.)
5. A backwater valve is installed in a building sewer, not a backflow preventer.
6. Show a vent for all fixture traps (e.g. the shower).