02/11/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the dishwasher drain from direct to indirect waste.
2. Route the rinse sink to the grease trap.
3. Provide flow control devices for the rinse sink and the 2-compartment sink. The flow control devices shall be readily accessible.
4. Provide a terminal cleanout for the floor sink located under the steam tables. (All fixtures having a horizontal drain, 5 feet or longer, require a cleanout. Sinks and urinals require a cleanout if they have any horizontal drain piping.)
5. A backwater valve is installed in a building sewer, not a backflow preventer.
6. Show a vent for all fixture traps (e.g. the shower).